dc.description.abstractMagistro baigiamajame darbe atliekama daugiabučio gyvenamojo pastato vienvamzdės šildymo sistemos veikimo analizė ir modeliuojami įvairūs šios sistemos subalansavimo variantai. Modeliavimui pasirenkama Design Builder programa, naudojantis jos funkcijomis sukuriamas pastato modelis. Iš pradžių išmatuojamos temperatūros dviejuose šildymo sistemos stovuose bei patalpose, kurias šie stovai aptarnauja. Matavimams pasirinktas 2018.01.09 – 2018.01.15 laikotarpis, gauti kiekvienos minutės temperatūriniai duomenys matuotuose taškuose. Pagal gautus temperatūrinius duomenis apskaičiuojama šildymo prietaisų galia. Nustačius šildymo prietaisų galias, apskaičiuojamas patalpų šilumos poreikis, kurį apskaičiavus atliekamas modelio kalibravimas pagal faktinius dydžius. Sukalibravus modelį, modeliuojami pastato variantai išlyginus temperatūrą visame pastate matavimo laikotarpiu. Galiausiai įvertinama nesubalansuotos šildymo sistemos modernizavimo bei protarpinio temperatūrinio žeminimo pritaikymo patalpose įtaka energijos suvartojimui ir pasiektam sutaupytos energijos kiekiui. Matavimo rezultatai atskleidė, kad daugiabutyje palaikoma nevienoda patalpų temperatūra. Tolstant nuo šilumos punkto, temperatūra ženkliai žemėja, su kiekvienu aukštu prarandama apie 1 ?C šilumos. Modeliavimo rezultatai atskleidė, kad esant įvairiems nesubalansuotos sistemos atvejams, atlikus sistemos modernizavimą, būtų galima sutaupyti iki 28,17 % šiluminės energijos. Taip pat parodė, kad taikant protarpinį temperatūrinį žeminimą, būtų galima sutaupyti iki 9,53 % energijos. Atlikus ekonominį vertinimą ir nustačius, PAL, TAL, VGN, GDV rodiklius paaiškėjo, kad šildymo sistemą modernizuoti naudinga tik tuo atveju, kai visas pastatas yra perkaitinamas ir jame palaikoma 20 C – 24 C temperatūra vertinant ekonominiu požiūriu. Darbo apimtis: 60 psl. teksto be preidų, 33 paveikslai, 21 lentelė, 25 bibliografiniai šaltiniai.lit
dc.description.abstractAnalysis of a single-pipe heating system performance analysis and models of various ways of balancing this system at multistorey residential building is carried out in this master thesis. The Design builder program is chosen for modeling, using its functions to create a building geometrical model. Initially, the temperature is measured in the two stands of the heating system and in the rooms served by these stands. The period from 2018 01 09 to 2018 01 15 was chosen for measurements, and each minute temperature data were obtained at measured points. According to the obtained temperature data, the heating power is calculated. After determining the capacity of the heating devices, the heat demand of the premises is calculated, which leads to calibration of the model according to actual values.Then various options when the temperature is equalized throughout the building during the measurement period are modeled. Finally, the impact of the upgrading of the unbalanced heating system and the application of intermitted temperature degradation in premises influence the energy consumption and achieved amount of saved energy is determined. The results of the measurements revealed that the multi-storey residential building maintains an uneven indoor temperature. From the heating point, the temperature is significantly lowered, with about of 1 °C of heat loss on each floor. The modeling results revealed that in the case of various unbalanced systems, up to 28,17 % of thermal energy could be saved through modernization of the system. It has also been shown that up to 9,53 % of energy can be saved through intermittent temperature degradation. After the economic evaluation and determination of SPP, RPP, IRR, NPV indicators have shown that the modernization of the heating system is only useful economically if the whole building is overheated and an average temperature of 20 °C – 24 °C. is maintained. Thesis consists of 60 psl. pages of text without appendixes, 33 pictures, 21 tables, 25 bibliographical entries.eng
dc.formatPDF
dc.format.extent60 p.
dc.format.mediumtekstas / txt
dc.language.isolit
dc.rightsPrieinamas tik institucijos intranete
dc.source.urihttps://talpykla.elaba.lt/elaba-fedora/objects/elaba:29029159/datastreams/MAIN/content
dc.titleDaugiabučio šildymo sistemos modernizavimo efektyvumas
dc.title.alternativeModernisation Effectiveness of Heating System at Multi-storey Residential Building
dc.typeMagistro darbas / Master thesis
dcterms.references0
dc.type.pubtypeETD_MGR - Magistro darbas / Master thesis
dc.contributor.institutionVilniaus Gedimino technikos universitetas
dc.subject.researchfieldT 006 - Energetika ir termoinžinerija / Energy and thermoengineering
dc.subject.studydirectionE13 - Energijos inžinerija / Energy engineering
dc.subject.ltŠildymas
dc.subject.ltmodernizacija
dc.subject.ltdaugiabutis
dc.subject.ltsubalansavimas
dc.subject.ltsureguliavimas
dc.subject.enHeating
dc.subject.enmodernization
dc.subject.enmulti-storey residential building
dc.subject.enbalancing
dc.subject.enadjustment
dc.identifier.elaba29029159


Šio įrašo failai

Thumbnail

Šis įrašas yra šioje (-se) kolekcijoje (-ose)

Rodyti trumpą aprašą