Assessment of different methods for designing bored piles

Thumbnail
Date
2012
Author
Gabrielaitis, Linas
Papinigis, Vytautas
Sirvydaitė, Jurgita
Metadata
Show full item record
Abstract
Straipsnyje nagrinėjami įvairūs skaičiavimo metodai, skirti gręžtiniams pamatams projektuoti. Lietuvos elektrinės teritorijoje projektuojant kombinuoto ciklo dujų turbinos bloko pamatus, dėl ypatingų statinio reikalavimų polių nuosėdžiams bei laikomajai gebai buvo parinkti gręžtiniai poliai. Pagrindinis darbo tikslas – įvertinti gręžtinių polių nuosėdžių ir laikomosios gebos skačiavimus pagal statinio zondavimo duomenis bei analitinius sprendimus, taikant skirtingus skaičiavimo metodus. Polio nuosėdžiams ir laikomajai gebai vertinti buvo taikyti šie metodai bei standartai: Bowles, Schmertmann, de Ruiter ir Beringen, Bustamante (LCPC), EN 1997-2 ir NEN 6743 standartų metodika. Remiantis statinio ir dinaminio zondavimo bei laboratorinių tyrinių duomenimis, suminio nuosėdžio reikšmė buvo gauta lygi 16 mm, iš jų 2 mm sudaro nuo vertikaliosios apkrovos gniuždomo polio deformacija. Tokio tipo statinių pagrindo nuosėdis negali būti didesnis nei 2 % polio skersmens. Atlikti skaičiavimai parodė, kad 800 mm skersmens ir 27 m ilgio polio visiškai pakanka statinėms ir dinaminėms apkrovoms atlaikyti.
 
Pilling foundation was evaluated performing immediate settlement analysis and included the examination of soil data received from cone and dynamic penetration tests, boreholes and laboratory tests. Soil properties were estimated taking into account investigation into the site of Elektrenai power plant and a soil exploration program developed according to Lithuanian standards. Pile settlement analysis showed that settlement value made 13.6 mm (pile toe settlement) and the settlement value of an elastic deformation of the pile from vertical compressive loads was 2.3 mm, for the most conservative situation. For such structure, foundation settlement should not exceed 16 mm. Elektrenai power plant has high reliability requirements, and therefore the pile having the diameter of 800 mm with a pile length of 27 m was adopted to endure overall loads.
 
Issue date (year)
2012
URI
https://etalpykla.vilniustech.lt/handle/123456789/135069
Collections
  • Straipsniai kituose recenzuojamuose leidiniuose / Articles in other peer-reviewed sources [8559]

 

 

Browse

All of DSpaceCommunities & CollectionsBy Issue DateAuthorsTitlesSubjects / KeywordsInstitutionFacultyDepartment / InstituteTypeSourcePublisherType (PDB/ETD)Research fieldStudy directionVILNIUS TECH research priorities and topicsLithuanian intelligent specializationThis CollectionBy Issue DateAuthorsTitlesSubjects / KeywordsInstitutionFacultyDepartment / InstituteTypeSourcePublisherType (PDB/ETD)Research fieldStudy directionVILNIUS TECH research priorities and topicsLithuanian intelligent specialization