Oro paruošimo įrenginio su dviem priešpriešinių srautų šilumogrąžiais efektyvumo tyrimas

Thumbnail
Date
2017
Author
Berneckaitė, Gerda
Martinaitis, Vytautas
Metadata
Show full item record
Abstract
Straipsnyje nagrinėjamas oro paruošimo įrenginys (OPĮ), su dviem priešpriešinių srautų šilumogrąžiais (PSŠ), esantis Vilniaus Gedimino technikos universiteto (VGTU) 8 aukšte Pastato energetinių ir mikroklimato sistemų (PEMS) laboratorijos patalpose. Tyrimo metu buvo išmatuotos efektyvumui nustatyti reikalingos į PSŠ įtekančio bei ištekančio oro temperatūros bei tiekiamo ir šalinamo oro srautai. Eksperimento metu išmatuoti duomenys buvo naudojami nustatant PSŠ1, PSŠ2 bei bendrą abiejų šilumokaičių temperatūros efektyvumą PSŠ. Priklausomai nuo į pirmąjį PSŠ įtekančios oro temperatūros (t1) sudarytas temperatūros efektyvumo kitimo grafikas. Įvertinus išmatuotas t1 temperatūros trukmes, sudaryta kumuliacinė kreivė bei PSŠ efektyvumo kitimo nuo t1 temperatūrų trukmės grafikas. Gauti duomenys parodė, jog PSŠ1 (85,8 – 94,4 %) temperatūrinis efektyvumas viso tyrimo metu buvo didesnis už PSŠ2 (73,7 – 86,0 %). Bendras abiejų šilumogrąžių efektyvumas kito nuo 93,8 iki 97,8 %.
 
The air handling unit (AHU) with two counter flow (CF) heat recovery units is analysed in this article. This unit is placed in Laboratory of Building Energy and Microclimate Systems (LBEMS) on 8th floor of Environmental Faculty of Vilnius Gediminas Technical University (VGTU). The values of the temperatures of the air that enters and leaves the CF were measured during the experiment. These measurements were used to determine the values of temperature efficiency of heat recovery units CF1, CF2 and CF. The diagram of the change of temperature efficiency depending on air temperature that enters the first CF (t1) was drawn. The cumulative curve and duration graph of efficiency change of CF depending on t1 temperature were made, when t1 values were measured and evaluated. Calculated values showed that CF1 (85.8 – 94.4%) temperature efficiency values are bigger than the values of CF2 (73.7 – 86.0%). Overall temperature efficiency of both CFs varies from 93.8% to 97.8% range.
 
Issue date (year)
2017
URI
https://etalpykla.vilniustech.lt/handle/123456789/117975
Collections
  • Konferencijų straipsniai / Conference Articles [15192]

 

 

Browse

All of DSpaceCommunities & CollectionsBy Issue DateAuthorsTitlesSubjects / KeywordsInstitutionFacultyDepartment / InstituteTypeSourcePublisherType (PDB/ETD)Research fieldStudy directionVILNIUS TECH research priorities and topicsLithuanian intelligent specializationThis CollectionBy Issue DateAuthorsTitlesSubjects / KeywordsInstitutionFacultyDepartment / InstituteTypeSourcePublisherType (PDB/ETD)Research fieldStudy directionVILNIUS TECH research priorities and topicsLithuanian intelligent specialization