Mažaenerginio administracinio pastato sezoninės energijos poreikių ypatybės

Thumbnail
Date
2012
Author
Subačiūtė, Ieva
Martinaitis, Vytautas
Metadata
Show full item record
Abstract
Nagrinėjamas mažaeneginis administracinis pastatas, esantis Vilniuje, Viršuliškių mikrorajone. Bendras pastato plotas siekia 3487 m2. Pastate yra įrengtos visos mikroklimato parametrus užtikrinančios sistemos: šildymo, mechaninio vėdinimo ir oro kondicionavimo. Naudojant modeliavimo priemonę TRNSYS (The Transient Energy System Simulation Tool) sukurti pastato ir atsinaujinančių energijos šaltinių panaudojimo jame modeliai. Saulės kolektoriuose gaunami energijos srautai panaudojami šildymui ir vėsinimui. Gauta, kad įrengus saulės kolektorius, kurių plotas 200 m2, vidutinės šildymo sezono metu reikalingos šildymo sistemos galios gali padengti 8 %. Vasaros metu iš saulės pagaminta vėsa gali padengti 26 % vėsinimo sistemai reikalingos galios.
 
The low energy office building in Vilnius Viršuliškės district is analysed. Total building area is 3487 m2. All the services ensuring the microclimate conditions: heating, mechanical ventilation and air conditioning systems are installed in the building. Using the simulation tool TRNSYS (The Transient Energy System Simulation Tool), there were developed the models of the building and of the renewable energy appliance in it. Energy flows of solar collectors are used for heating and cooling. It was calculated that the installation of solar collectors with an area of 200m2 could cover 8 % of heat demand for heating during the heating season. In summer the coolness generated from the sun could cover 26 % of cooling system demand.
 
Issue date (year)
2012
URI
https://etalpykla.vilniustech.lt/handle/123456789/134635
Collections
  • Konferencijų straipsniai / Conference Articles [15192]

 

 

Browse

All of DSpaceCommunities & CollectionsBy Issue DateAuthorsTitlesSubjects / KeywordsInstitutionFacultyDepartment / InstituteTypeSourcePublisherType (PDB/ETD)Research fieldStudy directionVILNIUS TECH research priorities and topicsLithuanian intelligent specializationThis CollectionBy Issue DateAuthorsTitlesSubjects / KeywordsInstitutionFacultyDepartment / InstituteTypeSourcePublisherType (PDB/ETD)Research fieldStudy directionVILNIUS TECH research priorities and topicsLithuanian intelligent specialization